Tube-Type FK-5-1-12 (Novec 1230) Fire Extinguishing Device (GAS-FK5112-TUB)
This thermally self-activating fire trace tube device uses Novec 1230, requires no power supply, automatically pressurizes with temperature rise, and operates down to -40°C – ideal for electrical cabinets and confined spaces.
Description
Product Description
The fire trace tube type Novec 1230 (FK-5-1-12, Perfluorohexanone) fire suppression device is a thermally self-activating, standalone fire suppression unit that requires no external power supply or complex control systems. The device uses a stainless steel sealed detection tube with no pre-stored pressure; as the ambient temperature rises, the pressure inside the tube automatically increases. When the temperature reaches approximately 100°C, the detection tube bursts and discharges the clean agent Novec 1230, providing fast, residue‑free fire suppression.
This device is cost-effective, maintenance-free, and has a service life of 5 to 10 years depending on installation conditions. No separate agent storage tank is needed. Optional pressure switches or signal units can be added for expanded functionality. The discharged agent is harmless to electrical components and personnel. Installation is simple and requires no special training. A pressure gauge allows real-time pressure monitoring. The device can operate at temperatures as low as -40°C.
It is particularly suitable for confined or hard‑to‑reach spaces such as electrical cabinets, cable trays, wind turbine nacelles, and lithium battery energy storage enclosures, and is capable of suppressing Class A, B, C, and E fires.
Suitable for confined spaces such as electrical cabinets, wind turbine nacelles, telecom base stations, lithium battery enclosures, cable trays/tunnels, vehicle battery compartments, and precision equipment interiors. Effective for incipient Class A, B, C, and E fires.
Certifications
Detailed information on product parameters
| Model | Agent | Agent weight (g) | Tube length (cm) | Outer diameter (mm) | Protected volume (m³) | Operating temp. (°C) | Static activation temp. (°C) |
| WZ-Q/T-100-QL | Novec 1230 | 250±5 | 100 | 18 | 0.25 | -40~80 | 110±10 |
| WZ-Q/T-200-QL | Novec 1230 | 500±5 | 200 | 18 | 0.50 | -40~80 | 110±10 |
| WZ-Q/T-300-QL | Novec 1230 | 750±5 | 300 | 18 | 0.75 | -40~80 | 110±10 |
| WZ-Q/T-400-QL | Novec 1230 | 1000±5 | 400 | 18 | 1.00 | -40~80 | 110±10 |
| WZ-Q/T-500-QL | Novec 1230 | 1250±5 | 500 | 18 | 1.25 | -40~80 | 110±10 |
Specifications
GAS-FK5112-TUB system
Detailed Table of System Devices
| Model number | Fire extinguishing agent | Medication quantity(g ) |
Chief Manager
(cm) |
Outer diameter (mm) | Protecting volume
(m³) |
Operating temperature↵(℃) | Static action temperature
(℃) |
| WZ-Q/T-100-QLe |
Novec12304 |
250±5 | 100 |
18↵ |
0.25 |
(-40~80) |
110±10 |
| WZ-Q/T-200-QL | 500±5 | 200 | 0.50 | ||||
| WZ-Q/T-300-QL | 750±5 | 300 | 0.75 | ||||
| WZ-Q/T-400-QLe | 1000±5 | 400 | 1.00 | ||||
| WZ-Q/T-500-QL | 1250±5 | 500 | 1.25 |
Certifications
Quality Assurance
Our systems are manufactured under strict quality control and certified by international bodies.
UL Listed
FM Approved
CE Certified
ISO 9001
ISO 14001
NFPA Compliant
Ready to Specify for Your Project?
Download the full technical datasheet or contact our engineering team for a customized proposal.