IG-100 Nitrogen Fire Extinguishing System

The IG-100 system uses 100% nitrogen as a clean agent – colorless, odorless, non-corrosive, non-conductive, leaves no residue, and maintains extinguishing concentration to prevent re-ignition.

Description

GAS-IG100-N2

Product Description

This system is available in two pressure ratings: 15 MPa and 20 MPa, using 100% pure nitrogen as the extinguishing agent. IG-100 is colorless, odorless, non-toxic, non-corrosive, and non-conductive. It is harmless to humans, produces no chemical byproducts during discharge, causes no secondary damage to equipment, and creates no fogging, ensuring safe egress. With a specific gravity of 0.97 relative to air, IG-100 maintains a stable extinguishing concentration after release, ensuring effective fire suppression and preventing re-ignition.   Suitable for fire protection in large computer rooms, communication centers, control rooms, valuable equipment rooms, cultural relic repositories, libraries and archives, data storage rooms, power plants, oil-immersed transformer rooms, rail transit, emergency power facilities, power

Certifications

GAS-IG100-N2

Detailed information on product parameters
Model QMD15/70 QMD15/80 QMD15/90 QMD15/120 QMD20/80 QMD20/82 QMD20/85 QMD20/90
Agent cylinder volume (L) 70 80 90 120 80 82 85 90
Agent fill weight (kg) 12.3 14 15.8 21 18.7 19.2 19.9 21.1
Max. working pressure (MPa) 17.2 17.2 17.2 17.2 23.2 23.2 23.2 23.2
Storage pressure (MPa) 15 15 15 15 20 20 20 20
Max. discharge time (s) ≤60 ≤60 ≤60 ≤60 ≤60 ≤60 ≤60 ≤60
Operating temperature (°C) 0 ~ 50 0 ~ 50 0 ~ 50 0 ~ 50 0 ~ 50 0 ~ 50 0 ~ 50 0 ~ 50
Minimum design concentration (%) 36 36 36 36 36 36 36 36
Nozzle working pressure (MPa) ≥2.0 ≥2.0 ≥2.0 ≥2.0 ≥2.0 ≥2.0 ≥2.0 ≥2.0
Applicable standard GB25972-2024 GB25972-2024 GB25972-2024 GB25972-2024 GB25972-2024 GB25972-2024 GB25972-2024 GB25972-2024
Design standards CECS312:2012, DBJ15-47-2022 CECS312:2012, DBJ15-47-2022 CECS312:2012, DBJ15-47-2022 CECS312:2012, DBJ15-47-2022 CECS312:2012, DBJ15-47-2022 CECS312:2012, DBJ15-47-2022 CECS312:2012, DBJ15-47-2022 CECS312:2012, DBJ15-47-2022

Specifications

IG100 gas fire extinguishing system

Detailed Table of System Devices

Model and specification QMD15 70 QMD15/ 80 QMD1 5/90 QMD15/1 20 QMD20/ 80 QMD20/8 2 QMD20/ 85 QMD20/9 0
Volume of fire extinguishing agent bottle group(L) 70 80 90 120 80 82 85 90
Filling amount of fire extinguishing agent(KG) 12.3 14 15.8 21 18.7 19.2 19.9 21.1
Maximum work pressure(MPa) 17.2 23.2
storage pressure (MPa) 15 20
Maximum injection time(S) ≤60
Working environment temperature(℃) 0℃~50
Minimum fire extinguishing design concentration(%) 36
Nozzle working pressure(MPa) 2.0
Implement standards GB25972-2024
Design standards CECS312:2012《Technical Regulations for Inert Gas Fire Extinguishing Systems》

DBJ15-47-2022《Design, Construction and Acceptance Specification for IG-100 Gas Fire Extinguishing System》

Certifications

Quality Assurance

Our systems are manufactured under strict quality control and certified by international bodies.

UL Listed

FM Approved

CE Certified

ISO 9001

ISO 14001

NFPA Compliant